Sens NRG24-20 Spezifikationen Seite 8

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 113
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 7
Cummins Northwest, LLC
Attachment to Quotation
-Exclusions-
Fuel System: Fuel for testing and initial fill of fuel.
Electrical: All off-engine wiring, field terminations of wiring, and lugs other than those
detailed in our submittal.
Mounting: Generator mounting bolts and anchors.
Miscellaneous: Third party electrical testing and certification, seismic certifications/calculations
for generator isolators only, coordination studies, stamped engineering
calculations, emissions testing, all other services and material not specifically
listed in the preceding quotation.
Documentation: Unless stated otherwise, four sets of O & M manuals are available upon request.
Electronic manuals are not available.
Taxes and Permits: Any applicable sales tax, permits, licenses.
All items listed
are excluded and will only be supplied by Cummins Northwest, LLC if agreed upon, in
writing, by a sales representative for Cummins Northwest, LLC.
Clarifications/Exceptions to Specifications: 263213 1.05K Cummins will assist the Contractor
with information needed to complete air quality permit. 1.05C & 2.02B 500 DFEK max output per
prototype testing is 516kw including all reserve factors. 2.10B 2 Circuit Breaker provided is a
Square D, PJ Series 1200AF/800AT, with ground fault indication only (no trip). 2.09D Load shed
control provided will be current sensing, rather than voltage sensing. 2.12 Pre-fitted enclosure
sound hoods are shipped separate, to be re-installed by Contractor at jobsite. 2.14 H. ATS-1 & 3
are oversized to meet drawing withstand ratings. 2.10 I. In-line current limiting fuse protection is
not provided within ATS’s. 2.10 G. Transfer switches are provided in Nema 1 enclosures stand-
alone, not designed for bus connection into a switchboard.
Current factory lead time is 13-15 weeks after drawing approvals.
-Terms and Conditions-
This offer and quotation incorporates and is contingent upon acceptance of the terms and
conditions in the standard Sales Order of Cummins Northwest, LLC. Purchase Orders or other
documents with terms and conditions that are inconsistent with the CNW standard Sales Order
will not be accepted unless agreed to in writing by an officer of Cummins Northwest, LLC.
Prices are valid for 30 days
If included in the quotation, all on-site startup, testing and training assumes weekdays, during
standard CNW business hours.
Additional charges may be added for work requested to be
done on overtime, weekends, and holidays.
F.O.B. factory, freight allowed to jobsite, off-loading is not included
Factory direct shipments require credit approval prior to shipment
Terms are C.O.D. or net 30 days
upon approval of credit
Equipment held for longer than 30 days may be charged a monthly storage fee
Cancellation charges are 25%
minimum after release of order
120204 rev. 2/07
Seitenansicht 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 112 113

Kommentare zu diesen Handbüchern

Keine Kommentare