NETWORK APPLICATIONS
POWERCOMMAND NETWORKS
N
ETWORK CABLING AND CONNECTIONS FOR FTT-10 NETWORKS
Network Topology
FTT-10 networks are designed to support free topology wiring, and will accommodate bus, star, ring,
or any combination of these topologies. Excepting the double-terminated bus topology, only one point
of termination is required for any free topology segment. Note that the actual termination circuit will
vary by application (See “Cable Termination” below.)
Network Nodes
Each device with an FTT-10 transceiver is a network node. The maximum number of nodes on a
network segment and on the total network is partly dependant on the network application. For
example, a network that is connecting only a few discrete variables between devices and has no
monitoring software attached could probably support 64 nodes (maximum allowable on a segment per
Echelon specs.) At the other extreme, a network with a large amount of inter-device bindings and
being monitored by PowerCommand PULSE with Reporting option would not be able to support
more than 12 devices using a single FTT-10 channel. However, with the appropriate addition of other
network management devices, the PULSE example could potentially support 64 devices or even
more. If there is any question about how many devices your network can support, contact the
Network Applications Engineer in the CPG System Sales department.
Network Cable Selection
The following cables are qualified for use with FTT-10 networks:
NEMA Level IV cable (Onan P/N 334-1350 [PVC] or 334-1351 [Plenum])
Belden 85102 or Belden 8471 (both are
single twisted pair)
TIA Category 5 (CAT5)
Network wiring should be run in separate conduit and installed following local electrical codes. Any
wire connected to Generator Sets must be stranded wire (NFPA110, Para. 7.12.4.1). Except when
using ring topology, cabling is not polarity sensitive. The average temperature of the wire should not
exceed +55ºC (+131ºF). Cable distance must comply with transmission specifications listed below.
The maximum total wire length is the total length of wire within a segment. The maximum node-to-
node distance is the maximum allowable distance between each individual node or the terminator.
Table 1 Free Topology
Maximum node-to-node
distance
Maximum total
Wire length
Belden 8471 1300 1600
Belden 85102 1600 1600
NEMA Level IV 1300 1600
TIA Category 5 800 1400
This information was accurate on the date published but Page 1 July 25, 2003
could change without notice.
* Optimal Cable
*
*