Enclosures
The transfer switch and control are mounted in a key-locking enclosure. Wire bend space complies with 2008 NEC.
Dimensions - transfer switch in UL type 1 enclosure
Depth
Amp rating Height Width
Door closed Door open
Weight Outline drawing
in mm in mm in mm in mm lb kg
40, 70, 125
3-pole
27.0 686 20.5 521 12.0 305 31.5 800 82 37 0310-0544
40, 70, 125
4-pole
35.5 902 26.0 660 16.0 406 41.0 1042 165 75 0500-4896
150, 225 35.5 902 26.0 660 16.0 406 41.0 1042 165 75 0310-0414
260 43.5 1105 28.5 724 16.0 406 43.0 1093 170 77 0310-0540
300, 400, 600 54.0 1372 25.5 648 18.0 457 42.0 1067 225 102 0310-1307
800, 1000 68.0 1727 30.0 762 20.6 524 48.5 1232 360 163 0310-0417
1000, 1200 76.3 1937 36.0 915 22.7 577 54.0 1372 450 204 0310-0482
1600, 2000* 90.0 2290 36.0. 915 48.0 1219 84.0 2134 1100 499 0310-0483
3000* 90.0 2290 36.0 915 48.0 1219 84.0 2134 1250 567 0310-0484
4000* 90.0 2290 46.5 1180 60.0 1520 106 2700 1850 839 0500-4485
Dimensions - transfer switch in UL type 3R, 4 or 12 enclosure
Depth
Amp rating Height Width
Door closed Door open
Weight
Cabinet
type
Outline
drawing
in mm in mm in mm in mm lb kg
40, 70, 125
3-pole
34.0 864 26.5 673 12.5 318 36.5 927 125 57 3R, 12, 0310-0453
3R, 12 0500-4896 40, 70, 125
4-pole
42.5 1080 30.5 775 16.0 406 44.0 1118 215 97
4 0500-4896
3R, 12 0310-0454
150, 225 42.5 1080 30.5 775 16.0 406 44.0 1118 215 97
4 0310-0446
3R, 12 0310-0455
260 46.0 1168 32.0 813 16.0 406 46.0 1168 255 102
4 0310-0447
3R, 12 0310-1315
300, 400, 600 59.0 1499 27.5 699 16.5 419 41.5 1054 275 125
4 0310-1316
3R, 12 0310-0457
800, 1000 73.5 1867 32.5 826 20.8 529 49.5 1257 410 186
4 0310-0449
1000, 1200 76.3 1937 36.0 915 22.7 577 54.0 1372 450 204 3R, 12, 4 0310-0482
1600, 2000* 90.0 2290 35.5 826 50.9 1293 80.0 2032 1100 499 3R, 12, 4 0310-0744
3000* 90.0 2290 38.0 965 51.0 1295 84.5 2146 1250 567 3R 0310-0745
4000* 90.0 2290 49.0 1244 60.0 1524 105 2654 1850 839 3R 0500-4486
Dimensions - transfer switch in UL type 4X stainless steel enclosure
Depth
A
mp rating Height Width
Door closed Door open
Weight
Cabinet
type
Outline
drawing
in mm in mm in mm in mm lb kg
40, 70, 125
3-pole
46.0 1168 32.0 813 16.0 406 46.0 1168 255 102 4X 0500-4184
40, 70, 125
4-pole
46.0 1168 32.0 813 16.0 406 46.0 1168 255 102 4X 0500-4896
150, 225 46.0 1168 32.0 813 16.0 406 46.0 1168 255 102 4X 0500-4184
260 46.0 1168 32.0 813 16.0 406 46.0 1168 255 102 4X 0500-4184
300, 400, 600 73.5 1867 32.5 826 19.5 495 49.5 1257 410 186 4X 0500-4185
800, 1000 73.5 1867 32.5 826 19.5 495 49.5 1257 410 186 4X 0500-4185
1000, 1200 70.0 1778 40.0 1016 19.8 502 59.0 1499 450 204 4X 0306-5300
1600,2000 90.0 2290 35.5 826 50.9 1293 80.0 2032 1100 499 4X 0310-0744
* Rear or side access is required to complete power wiring installations.