Our energy working for you.™
www.cumminspower.com
©2008|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand, InPower, AmpSentry, iWatch and “Our energy working for you.”
are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
S-1444h (4/08) Page 3 of 10
scrolling through screens with the navigation keys. The
top three lines of the display are allocated to mode and
status messages that continuously display the operating
mode of the control system, as well as any faults or
warning conditions that may be present on the controller.
If more than one fault or warning message is present, the
messages will scroll to allow the operator to view all active
messages in the system.
Screen-saver mode - The operator panel can be
programmed to automatically switch off to reduce battery
voltage drain when the control is not being used and the
generator set is not running. Depressing any button on the
operator panel, new fault conditions or receipt of a remote
signal at the control will “wake up” the control.
Generator set data
Generator set hardware data - Generator set rating in
kVA, complete generator set model number and serial
number, engine model and serial number and alternator
model and serial number. The control also displays the
part number of the control and the software version
present in the control.
Data logs - Number of start attempts and number of start
attempts since reset. Number of times generator set has
run and number of times since reset. Duration of
generator set running time and duration of running time
since last reset. Generator set kWh produced and kWh
produced since last reset.
Adjustment history - Record of adjustment and setting
changes made on the control, identifies whether
adjustment was made via the operator panel or with a
service tool. If a service tool is used, the control provides
a record of the serial number of the tool used. This
information is read with InPower.
Fault history - Record of the most recent fault conditions
with time stamp, along with the number of times each fault
has occurred. At least 20 events are stored in the control
memory.
Load profile data - Data indicating the total operating
hours at percent of load in 10% increments and since
reset.
Generator set AC data
Generator set output frequency, voltage and
current - All phases (line-to-line and line-to-neutral for
voltage. Accuracy 1%.
Generator set power output - PowerCommand
displays generator set kW and kVA output (average phase,
individual phase and direction of flow) and power factor
with leading/lagging indication. Accuracy 5%.
Generator set kWh energy output - Total kWh
produced and total produced since last reset with time
stamp of time of last reset.
Digital synchroscope - Bus voltage and frequency,
generator set bus voltage and frequency, the phase angle
displacement and a signal indicating “ready to close”. A
breaker control switch is included on this panel for
convenient operation of the equipment without switching
between viewing screens.
Engine data
Basic engine data - Engine starting battery voltage,
engine lube oil pressure and engine coolant temperature.
Engine service data - Varies with engine used, but
typically includes: Engine coolant pressure, engine fuel rail
temperature and pressure, engine fuel input and output
temperature, intake manifold temperature and pressure,
ambient air pressure, crankcase blowby flow and
aftercooler inlet coolant temperature.
Engine fuel consumption - The fuel consumed by the
engine is calculated by the control based on fuel flow into
the engine and returned by the engine, and the
temperature of the two flow streams. Accuracy is +
5%
over 500 hours of operation. Data provided includes
overall average fuel consumed and consumption since
reset. This information is read with InPower.
Engine exhaust temperature (optional).
Power transfer control data (optional)
Utility (mains) source data - Displays line-to-line and
line-to-neutral voltage of utility (mains) source, frequency
and estimated amps, and kW and kVA supplied by utility
(mains) source (optional when power transfer control is
used).
System status information - Provides graphical
system status display showing availability of sources and
positions of each contactor.
System control - Allows operator to view status of
system and manually control operation of the system.
Provides manual adjustment capability for time delay start,
stop, transfer and retransfer, as well as time delays for
program transition (when used) and power transfer overlap
time.
Internal control functions
General functions
System control voltage - The control operates on 24
VDC from the generator set starting batteries. Control
functions are fully operational over a voltage range of 8
VDC to 36 VDC.
Emergency start mode - PowerCommand accepts a
ground signal from remote devices or a network signal to
automatically start the generator set and immediately
accelerate to rated speed and voltage.
PowerCommand includes a smart starting system that is
designed to quickly start the engine, minimize black
smoke, minimize voltage and frequency overshoot, and