Operator panel
The operator panel provides the user with a complete
package of easy to view and use information. It includes
an enhanced graphical operator panel that allows the user
to view up to 9 lines of information, as well as graphical
displays of system data. Connections to the operator
panel are sealed, locking plug interfaces for reliable,
vibration-resistant interconnection to the generator set
wiring harness.
Control switches and functions
Off/manual/auto mode control switch - The not in
auto lamp will flash when the control is in the manual or off
mode. In the auto mode, the generator set can be started
using the exercise push-button or with a start signal from a
remote device, such as automatic transfer switches.
Manual run/stop control switch and indicating
LED - When the mode control switch is in the manual
position and the manual run/stop switch is pressed, the
generator set will start, bypassing all time delay starts.
(Time delay idle can also be bypassed with another control
action.) If the generator set is running in the manual mode,
pressing the run/stop switch will cause the generator set to
shut down. An LED (light emitting diode) lamp adjacent to
the switch will light to indicate the generator set is in
manual mode.
Exercise control switch and indicating LED - When
the mode control switch is in the auto position the exercise
control switch is used to complete a pre-programmed
exercise sequence. All exercise functions are disabled
when an emergency start command is received by the
control. An LED lamp adjacent to the switch will light to
indicate the generator set is in exercise mode.
Panel lamp/lamp test control switch.
Fault acknowledge/reset switch - The control
includes a fault acknowledge function to allow the operator
to reset the fault condition. If the fault condition is not
corrected, the fault will reappear, but will not be logged as
a separate event. Multiple faults can be logged and
displayed at one time.
Emergency stop control switch.
Operator adjustments - The control includes provisions
for many set up and adjustment functions via raise/lower
switches on the operator panel. Functions that can be
adjusted by the operator include:
- Time delay start (0-300 seconds)
- Time delay stop (0-600 seconds)
- Alternator voltage (+
5%)
- Alternator frequency (+
3 Hz)
The operator panel can be configured to require an access
code prior to adjusting these values. A second access
code is used to protect the control from unauthorized
service level adjustments. Voltage and frequency
adjustments are disabled during operation in parallel with a
system bus to prevent inadvertent misadjustment of the
paralleling load sharing functions.
Analog AC metering panel
The PowerCommand control is equipped with an analog
AC metering panel that simultaneously displays 3-phase
line-to-line AC volts and current, kW, power factor and
frequency.
The meter panel is composed of a series of LEDs
configured in bar graphs for each function. The LEDs are
color coded with green indicating normal range values,
amber for warning levels and red for shutdown conditions.
Scales for each function are in % of nominal rated values.
Graphical display panel
The PowerCommand control is provided with a graphical
display capable of displaying up to 9 lines of data with
approximately 27 characters per line. The graphical
display is accompanied by a set of six tactile-feel
membrane switches that are used by the operator to
navigate through control menus and to make control
adjustments. Display is configurable for multiple
languages. It is configurable for units of measurement.
The display incorporates three levels of operation and
adjustability. All data on the control can be viewed by
Seitenansicht 26