Sens NRG24-20 Spezifikationen Seite 53

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 79
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 52
Our energy working for you.™
www.cumminspower.com
©2007|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand and “Our energy working for you.” are trademarks of Cummins
Power Generation. Other company, product, or service names may be trademarks or service marks of others.
S-1472c (9/07)
Specifications
Signal requirements
Positive - Input impedance is 1.82 kOhms to ground;
maximum input voltage = 31 VDC.
Negative - Input impedance is 1.82 kOhms to Bat+:
inputs are at Bat+ level when open.
Sink/source current threshold for detection - 150 uA
minimum, 3 mA maximum.
Typical conductor size: 16 ga for 304.8 m (1000 ft)
Max conductor size for terminal: 12 ga
Relay outputs
0.2 A at 125 VAC and 1 A at 30 VDC
Network connections
18 ga twisted pair wire or Cat 5 cable. Total network
length can not exceed 1219 m (4000 ft). Up to 20 nodes
can be connected to the network.
Note: Any communications wire connected to the
generator set should be stranded cable.
Power
Maximum consumption: 15 watts
Battery voltage
Functional range - Audible and visual conditions
operational from 6.5 to 31 VDC.
Low voltage setting - 12.0 VDC for 12 Volt nominal
systems; 24.0 for 24 Volt nominal systems.
High voltage setting - 16.0 Volt for 12 Volt nominal
systems; 32.0 Volt for 24 Volt nominal systems.
Alarm horn
Sound level: 90 dB at 30 cm
Physical
Weight (with enclosure): 1.4 kg (3.0 lbs)
Temperature
-20 °C to +70 °C (-4 °F to +158 °F)
Humidity
10% to 95% RH (non-condensing)
Default lamp configurations
Can be configured for current NFPA 110 standard or as a replacement for Legacy (pre-2001) NFPA 110 annunciator
(300-4510 or 300 4511)
NFPA 110
L
amp Description Colo
r
Horn
Flash
DS1
Customer fault 1
Green No No
DS2
Customer fault 2
Amber No No
DS3
Customer fault 3
Red No No
DS4
Genset su
pp
l
y
in
g
load
Amber No No
DS5
Char
g
er AC failure
Amber Yes No
DS6
Low coolant level
Amber Yes No
DS7
Low fuel level
Red Yes No
DS8
Check
g
enerator set
Amber No No
DS9
Not in auto
Red Yes Yes
DS10
Generator set runnin
g
Amber No No
DS11
Hi
g
h batter
y
volta
g
e
Amber Yes No
DS12
Low batter
y
volta
g
e
Red Yes No
DS13
Weak batter
y
Red Yes No
DS14
Fail to start
Red Yes No
DS15
Low coolant tem
p
Red Yes No
DS16
Pre-hi
g
h en
g
ine tem
p
Amber Yes No
DS17
Hi
g
h en
g
ine tem
p
Red Yes No
DS18
Pre-low oil
p
ressure
Red Yes No
DS19
Low oil
p
ressure
Red Yes No
DS20
Overs
p
eed
Red Yes No
Seitenansicht 52