S-1566b (4/08) Page 4 of 6
Emergency stop
Annunciated whenever either emergency stop signal is
received from external switch.
Hydro mechanical fuel system engine
protection
Overspeed shutdown - Default setting is 115% of
nominal.
Low lube oil pressure warning/shutdown
- Level is preset
(configurable with InPower) to match the capabilities of
the engine used. Control includes time delays to prevent
nuisance shutdown signals.
High lube oil temperature warning/shutdown
- Level is
preset (configurable with InPower) to match the
capabilities of the engine used. Control includes time
delays to prevent nuisance shutdown signals.
High engine temperature warning/shutdown
- Level is
preset (configurable with InPower) to match the
capabilities of the engine used. Control includes time
delays to prevent nuisance shutdown signals.
Low coolant temperature warning
– Indicates that engine
temperature may not be high enough for a 10 second
start or proper load acceptance.
Sensor failure indication
- Logic is provided on the base
control to detect analog sensor or interconnecting wiring
failures.
Full authority electronic engine protection
Engine fault detection is handled inside the engine ECM.
Fault information is communicated via the SAE-J1939
data link for annunciation in the HMI.
General engine protection
Low and high battery voltage warning - Indicates status
of battery charging system (failure) by continuously
monitoring battery voltage.
Weak battery warning
- The control system will test the
battery each time the generator set is signaled to start
and indicate a warning if the battery indicates impending
failure.
Fail to start (overcrank) shutdown
- The control system
will indicate a fault if the generator set fails to start by the
completion of the engine crack sequence.
Fail to crank shutdown
- Control has signaled starter to
crank engine but engine does not rotate.
Cranking lockout
- The control will not allow the starter to
attempt to engage or to crank the engine when the
engine is rotating.
Alternator protection
High AC voltage shutdown (59) - Output voltage on any
phase exceeds preset values. Time to trip is inversely
proportional to amount above threshold. Values
adjustable from 105-130% of nominal voltage, with time
delay adjustable from 0.1-10 seconds. Default value is
110% for 10 seconds.
Low AC voltage shutdown (27)
- Voltage on any phase
has dropped below a preset value. Adjustable over a
range of 50-95% of reference voltage, time delay 2-20
seconds. Default value is 85% for 10 seconds.
Overcurrent warning/shutdown
- Implementation of the
thermal damage curve with instantaneous trip level
calculated based on current transformer ratio and
application power rating.
Under frequency shutdown (81 u) - Generator set output
frequency cannot be maintained. Settings are adjustable
from 2-10 Hz below nominal governor set point, for a
5-20 second time delay. Default: 6 Hz, 10 seconds.
Over frequency shutdown/warning (81o
) - Generator set
is operating at a potentially damaging frequency level.
Settings are adjustable from 2-10 Hz above nominal
governor set point for a 1-20 second time delay. Default:
6 Hz, 10 seconds, enabled.
Loss of sensing voltage shutdown
- Shutdown of
generator set will occur on loss of voltage sensing inputs
to the control.
Field overload shutdown
- Uses field voltage to
shutdown generator set when a field overload condition
occurs.
Field control interface
Input signals to the base control include:
- Remote start
- Local and emergency stop
- Configurable inputs: Control includes (4) input signals
from customer discrete devices that are configurable
for warning, shutdown or status indication, as well as
message displayed