Sens NRG24-20 Betriebsanleitung Seite 16

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 16
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 15
SENS EnerGenius Technical Manual
16
Service hotline: 1.800.742.2326
1.303.678.7500
RELAY
CONTACTS
BATTERY
FAULT
ALARM
AC FAIL
ALARM
CHARGER
FAIL
ALARM
HIGH BATTERY
ALARM
(HI DC)
LOW BATTERY
ALARM
(LO DC)
COMMON TB5-1
COM
TB5-4
COM
TB5-7
COM
TB5-10
COM
TB5-13
COM
OPEN ON
ALARM
TB5-2
OK
TB5-5
OK
TB5-8
OK
TB5-11
OK
TB5-14
OK
CLOSE ON
ALARM
TB5-3
FAIL
Defaults to OK
with no AC
input
TB5-6
FAIL
Defaults to
Fail with no
AC input
TB5-9
FAIL
Defaults to
OK with no
AC input
TB5-12
FAIL
Defaults to OK
with no battery
TB5-15
FAIL
Defaults to fail
with no battery
C. ALARM DESCRIPTION, FIVE ALARM MODEL:
NORMAL SET UP:
1. Elect the voltmeter function by sliding the meter switch to the “V” position.
2. Apply AC power by closing the branch circuit breaker and any other disconnect devices.
3. The meter display should light immediately after power on and display the battery voltage. The green
AC/ ON LED should be lighted. If a temperature sensor is present, either internal or remote, the green
T-COMP (Temperature Compensation) LED should be lighted.
4. After a short delay (typically 10 seconds or less), the charger will produce output. The voltmeter reading should
increase, indicating the battery is being charged.
5. Change the meter switch to the “A” position to read output current.
Current should be close to 20A if the battery requires recharging. If automatic boost is enabled, the BOOST
MODE LED may light, in which case the battery will be charged until it reaches 106% of the float voltage. If
boost is disabled, the green FLOAT MODE LED should be on and the battery will charge until it reaches the
float voltage setting.
Output current will be low if the battery is fully charged, possibly too low to read on the meter. This is normal,
provided the correct charging voltage is present. The green FLOAT MODE LED should light up when output
current is below approximately 18A.
Seitenansicht 15